Fitting skylights does not automatically lower your electricity bill. Daylight harvesting does. Here is how to pair polycarbonate rooflights with lighting controls in Indian factories and warehouses.
Many factory owners fit skylights, then walk into the shed at noon and find every LED fixture still burning at full power. The roof is bright, the meter is unchanged, and the skylight gets blamed. The problem is rarely the skylight. It is the missing link between daylight and the lighting circuit.
That link is called daylight harvesting. This guide explains what it is, what it needs, and how to design it for Indian industrial buildings using polycarbonate rooflights.
Daylight harvesting means using sensors and controls to reduce electric lighting automatically when enough natural light is available. Rooflights supply the daylight. A photocell measures it. A controller then dims or switches off the fixtures nearest the skylights so you only pay for light you actually need.
Without controls, a skylight improves the look of a space but saves almost nothing, because the electric lights keep running on the same timer or manual switch as before. With controls, the saving follows the daylight: highest on bright days and in zones close to the openings.
For a wider view of the energy argument, read daylighting and warehouse energy savings.
The amount of daylight reaching the floor depends on rooflight area relative to floor area, the light transmission of the sheet, roof height and room reflectance. A common starting point in industrial design is to provide rooflights over a modest percentage of the roof area, then confirm with a daylight simulation. Our explainer on daylight factor and rooflight area ratio covers the maths.
Evenness matters as much as quantity. Widely spaced, uniformly distributed rooflights give a steady level across the floor. A few large openings create bright patches and dark zones, which makes harvesting harder because sensors see very different conditions. Diffusing or opal sheet helps spread light. See roof monitors versus skylights for layout options.
A photosensor reads the light level at the work plane or near the ceiling. Place it where it sees daylight representative of its zone, away from direct sun spots and reflective machinery. Each sensor should control a defined group of luminaires, not the whole building.
Dimmable LED drivers allow smooth reduction, which is least noticeable to workers. Stepped switching, for example turning off alternate rows, is cheaper and can work well in warehouses where fine control is not needed. Either way, the aim is to hold a target lux level, not to chase zero lighting.
Divide the floor into zones parallel to the rooflight rows:
Each zone gets its own sensor and circuit. This is why simply adding skylights to an old layout, where all fixtures share one switch, saves so little.
Sheet choice affects both the daylight you harvest and the comfort you protect:
For PEB roofs, profile-matched corrugated sheet makes installation straightforward. Our PEB skylight specification guide lists what to confirm.
Treat this as a screening exercise. Actual savings depend on your building, climate, tariff and how well the system is commissioned, so ask for a project-specific calculation before committing.
Coxwell supplies UV-protected polycarbonate rooflights for factories, warehouses and PEB sheds across India, and our technical team can advise on sheet type, layout and rooflight area for your building. Share your roof drawings and operating pattern and we will recommend a specification. Contact Coxwell for a quotation and technical support.
It is the use of photosensors and controls to dim or switch off electric lights automatically when enough natural light is available, so skylights translate into real electricity savings.
Not usually. If the electric lights keep running at full power during the day, a skylight saves little. Savings come when sensors and dimming or switching reduce lighting in response to daylight.
Dimmable LED drivers give smooth, unnoticeable reduction, while stepped switching is cheaper and works well where fine control is unnecessary. The right choice depends on the task and budget.
A UV-protected multiwall or profiled sheet with good diffusion and appropriate heat control, so light is spread evenly without adding unwanted heat or glare.
Next step
Our team can help you specify the right system, review your BOQ, or answer technical questions about your project.